Description
Part of the groov EPIC® system, the GRV-OAC-12 digital output module can switch up to 12 separate AC loads of 12-250 VAC each. The module provides 300 volts of transient protection for sensitive control electronics from industrial field signals. AC outputs are zero voltage turn on and zero current turn off to minimize transients during switching. The module cover includes an LED that indicates status and a touch-sensitive pad. Touch the pad and the groov EPIC processor displays information about the module, including specifications and a wiring diagram.